| Plan Review Notes For Permit 12070517 |
| Permit Number |
12070517 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-24 16:24:58 | REVISION MECHANICAL REVIEW COMMENTS. | | | CODE: 2007 FBC W/ 2009 REVISIONS. | | | | | | 1- INFORMATION ON ENERGY CALCULATIONS, RESIDENTIAL | | | SYSTEM SIZING CALCULATIONS AND EQUIPMENT SIZE | | | INFORMATION ON SHEET M-1 DON'T MATCH. REVISE AS | | | REQUIRED. | | | SEC. 106.1.1 AND SEC. 13-607.AB.1. | | | CHECK TOTAL LOAD CALCULATIONS, SEER, ETC. | | | | | | 2- COOLING EQUIPMENT CAPACITY CAN'T BE MORE THAN 1.15 | | | TIMES GREATER THAN THE TOTAL LOAD CALCULATED. REVISE AS | | | REQUIRED TO COMPLY. SEC. 13-607.AB.1.1. | | | COORDINATE WITH THE ENERGY CALCULATIONS, EQUIPMENT | | | SIZING CALCULATIONS AND PLAN M-1. | | | | | | 3- TRANSFER DUCTS SHOWN ON PLAN M-1 FOR MASTER BEDROOM | | | AND ADJACENT BEDROOM DON'T COMPLY WITH THE BALANCED | | | RETURN AIR SEC. M1602.4. REVISE AS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|