2012-07-24 16:24:58REVISION MECHANICAL REVIEW COMMENTS.
 CODE: 2007 FBC W/ 2009 REVISIONS.
  
 1- INFORMATION ON ENERGY CALCULATIONS, RESIDENTIAL
 SYSTEM SIZING CALCULATIONS AND EQUIPMENT SIZE
 INFORMATION ON SHEET M-1 DON'T MATCH. REVISE AS
 REQUIRED.
 SEC. 106.1.1 AND SEC. 13-607.AB.1.
 CHECK TOTAL LOAD CALCULATIONS, SEER, ETC.
  
 2- COOLING EQUIPMENT CAPACITY CAN'T BE MORE THAN 1.15
 TIMES GREATER THAN THE TOTAL LOAD CALCULATED. REVISE AS
 REQUIRED TO COMPLY. SEC. 13-607.AB.1.1.
 COORDINATE WITH THE ENERGY CALCULATIONS, EQUIPMENT
 SIZING CALCULATIONS AND PLAN M-1.
  
 3- TRANSFER DUCTS SHOWN ON PLAN M-1 FOR MASTER BEDROOM
 AND ADJACENT BEDROOM DON'T COMPLY WITH THE BALANCED
 RETURN AIR SEC. M1602.4. REVISE AS REQUIRED.
  