| Date |
Text |
| 2012-07-23 15:57:30 | BUILDING PLAN REVIEW |
| | PERMIT: 12070514 |
| | ADD: 300 OKEECHOBEE BLVD VS 901 S OLIVE? |
| | CONT: ROBLING ARCHITECTURE CONSTRUCTION, INC |
| | TEL: (561)662-0000 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THE WORK TO BE |
| | COMPLETED UNDER THIS PERMIT IS TO BE LOCATED AT 300 |
| | OKEECHOBEE BLVD OR PALM BEACH ATLANTIC CHAPEL WHERE AS |
| | THE TITLE BLOCK OF THE PLANS INDICATES THE PROJECT TO |
| | BE LOCATED AT 901 S OLIVE PEMBROKE HALL, PLEASE MAKE |
| | CORRECTION TO THE LOCATION? ADDITIONAL INFORMATION |
| | REQUIRED 107.2.1.3. |
| | |
| | 2) PLEASE PROVIDE THE MINIMUM BUILDING TPYE, 2010 FBC- |
| | B 107.3.5.1.1(3)*. |
| | |
| | 3)SHEET A-1PLEASE REVIEW PLATFORM CONSTRUCTION |
| | REQUIREMENTS: 410.4 PLATFORM CONSTRUCTION. PERMANENT |
| | PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS AS REQUIRED |
| | FOR THE TYPE OF CONSTRUCTION OF THE BUILDING IN WHICH |
| | THE PERMANENT PLATFORM IS LOCATED. PERMANENT PLATFORMS |
| | ARE PERMITTED TO BE CONSTRUCTED OF |
| | FIRE-RETARDANT-TREATED WOOD FOR TYPE I, II, AND IV |
| | CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30 |
| | INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN |
| | ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN |
| | 3,000 SQUARE FEET (279 M2) IN AREA. WHERE THE SPACE |
| | BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR |
| | ANY OTHER PURPOSE OTHER THAN EQUIPMENT, WIRING OR |
| | PLUMBING, THE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN |
| | 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE |
| | SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR |
| | EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE |
| | PERMANENT PLATFORM NEED NOT BE PROTECTED. |
| | |
| | 4) SHEET A-12010 FBC-B 1009.6 STAIRWAY CONSTRUCTION. |
| | ALL STAIRWAYS SHALL BE BUILT OF MATERIALS CONSISTENT |
| | WITH THE TYPES PERMITTED FOR THE TYPE OF CONSTRUCTION |
| | OF THE BUILDING, EXCEPT THAT WOOD HANDRAILS SHALL BE |
| | PERMITTED FOR ALL TYPES OF CONSTRUCTION. |
| | |
| | 5) SHEET A-1 PLANS ARE MISSING DETAILS FOR HANDRAILS. |
| | 2010 FBC-B 1009.12 STAIRWAYS SHALL HAVE HANDRAILS ON |
| | EACH SIDE AND SHALL COMPLY WITH SECTION 1012. |
| | |
| | 6) SHEET A-2 IT APPEARS THE WORK BEING COMPLETED ON |
| | THIS SHEET INDICATED BY THE KEY PLAN APPEARS TO BE |
| | WITHIN A DIFFERENT BUILDING, POSSIBLY A DIFFERENT |
| | ADDRESS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |