| Plan Review Notes For Permit 12070481 |
| Permit Number |
12070481 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-16 13:37:12 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- ENGINEERING CALCULATIONS ARE BASED ON 3 FEET HIGH | | | PARAPET AROUND ENTIRE ROOF. VERIFY SIZE OF PARAPET. | | | OTHERWISE, CALCULATIONS NEED TO BE REVISED. | | | | | | 2- VERIFY THAT RE-ROOF IS DONE ON ENTIRE ROOF. 1000 SF. | | | AS SPECIFIED ON PERMIT APPLICATION. |
|