2012-07-23 11:33:39****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 1207.3, PRODUCT TO BE TESTED IN ACCORDANCE WITH
 ASTM E 492, PRODUCT BROCHURE NOT CLEAR, STATES IT WAS
 TESTED TO ASTM E 2179. MANUFACTURER (OR LOCAL
 DISTRIBUTOR) IS AWARE OF THIS REQUIREMENT AND WAS TO
 PROVIDE EITHER TEST OR SUBMIT INFORMATION UNDER
 ALTERNATIVE MATERIALS & METHODS FBC 104.11.
  
 2. SEE FBC 1207.2, PRODUCT TO BE TESTED IN ACCORDANCE
 WITH ASTM E 90 FOR STC, CANNOT BE ESTIMATED AS STATED
 ON MANUFACTURER'S BROCHURE (SUBMITTED BY CONTRACTOR).
  
 3. FBC 603.1(2), FLAME SPREAD INDEX OF NOT MORE THAN
 200 IS REQUIRED, PLEASE SUBMIT TEST REPORT OR OTHER
 DATA.
  
  
  