| Plan Review Notes For Permit 12070479 |
| Permit Number |
12070479 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-23 11:33:39 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FBC 1207.3, PRODUCT TO BE TESTED IN ACCORDANCE WITH | | | ASTM E 492, PRODUCT BROCHURE NOT CLEAR, STATES IT WAS | | | TESTED TO ASTM E 2179. MANUFACTURER (OR LOCAL | | | DISTRIBUTOR) IS AWARE OF THIS REQUIREMENT AND WAS TO | | | PROVIDE EITHER TEST OR SUBMIT INFORMATION UNDER | | | ALTERNATIVE MATERIALS & METHODS FBC 104.11. | | | | | | 2. SEE FBC 1207.2, PRODUCT TO BE TESTED IN ACCORDANCE | | | WITH ASTM E 90 FOR STC, CANNOT BE ESTIMATED AS STATED | | | ON MANUFACTURER'S BROCHURE (SUBMITTED BY CONTRACTOR). | | | | | | 3. FBC 603.1(2), FLAME SPREAD INDEX OF NOT MORE THAN | | | 200 IS REQUIRED, PLEASE SUBMIT TEST REPORT OR OTHER | | | DATA. | | | | | | | | | |
|