| 2012-07-17 10:04:30 | RESIDENTIAL (R3) FLAT ROOF RE-ROOF BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA 12-0227.18 SUBMITTED. | | | NEED THE CALCULATIONS TO MEET THE DESIGN PRESSURES | | | REQUIRED BY SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | | | | ***NOTE: WHEN DOING THE CALCULATIONS TAKE INTO | | | CONSIDERATION THAT THIS BUILDING IS LOCATED ON EXPOSURE | | | "D". SEE SEC. R301.2.1.4.3. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. THE PERMIT FEE | | | BALANCE IS $159.52. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | [email protected] |
|