| Plan Review Notes For Permit 12070466 |
| Permit Number |
12070466 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-17 11:03:24 | 1601 FORUM PLACE: SUITE #805 | | | PERMIT #12070466 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE | | | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | | UPWARD MOVEMENT. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|