| Plan Review Notes For Permit 12070422 |
| Permit Number |
12070422 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-14 20:10:53 | 1711 WORTHINGTON ROAD - BUILDING "A" & "B" | | | PERMIT #12070414 & #12070422 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO- SUBMIT REVISION WITH THE FOLLOWING | | | INFORMATION***** | | | | | | SUBMIT CUTSHEETS FOR EQUIPMENT TO BE INSTALLED. | | | | | | PROVIDE A SMOKE DETECTOR IN THE ELECTRICAL ROOM HOUSING | | | THE NAC POWER EXTENDER. | | | | | | EACH BUILDING SHALL BE ANNUNCIATED SEPARATELY. PROVIDE | | | A GRAPHIC ANNUNCIATOR (OR SIMILAR), THAT WILL ALLOW | | | EMERGENCY RESPONDERS TO QUICKLY IDENTIFY IF THE ALARM | | | CONDITION IS LOCATED IN BUILDING "A" OR BUILDING "B." | | | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | NOTE: WHERE THE FIRE ALARM CIRCUITS ENTER OR EXIT | | | BUILDINGS, THE CIRCUITS AND EQUIPMENT SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE NEC (NFPA 70) SECTION | | | 760.32. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|