Plan Review Notes
Plan Review Notes For Permit 12070388
Permit Number 12070388
Review Stop E
Sequence Number 1
Notes
Date Text
2012-08-06 08:12:0612070388
 1400 CENTREPARK BLVD.
 T-MOBILE SERVICE UPGRADE
  
 INDICATE THE LOCATION OF THE NEW 50 KW TRANSFORMER. NEC
 215.5
 PROVIDE OVER CURRENT PROTECTION FOR THE SECONDARY SIDE
 OF THE TRANSFORMER. NEC 225.31
 PROVIDE A SUMMARY LOAD CALCULATION FOR THE EXISTING
 600A 3 PHASE PANEL. NEC 215.2
 PROVIDE AN ELECTRICAL SYSTEM BONDING AND GROUNDING
 SCHEMATIC. NEC 250.4 250.20
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  