| Plan Review Notes For Permit 12070387 |
| Permit Number |
12070387 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-23 14:35:49 | FBC PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. NO DRINKING FOUNTAIN WAS FOUND ON THE PLANS. | | | BUSINESS OCCUPANCIES WITH OVER 15 OCCUPANTS REQUIRE | | | DRINKING FOUNTAINS THAT MEET TABLE 403.1 AND THE | | | FLORIDA ACCESSIBILITY CODE | | | 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING | | | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN | | | SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING | | | FOUNTAIN SHALL COMPLY WITH 602.7. | | | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES | | | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE | | | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING | | | FOUNTAINS. | | | ***NOTE***: | | | PLEASE SHOW LOCATION OF DRINKING FOUNTAIN IF ONE EXISTS | | | ALREADY FOR THIS FLOOR. | | | | | | 2. NO DETAIL WAS FOUND FOR THE LOUNGE SINK. | | | FBC ACCESSIBILITY 602.2 CLEAR FLOOR SPACE COMPLYING | | | WITH 305 & 306 OR EXCEPTION #1 SIDE APPROACH WITH SINK | | | CENTERED A MINIMUM OF 24" FROM SIDE WALL IS REQUIRED. | | | 606.3 COUNTER TOP OR SINK RIM SHALL BE A MAXIMUM OF 34" | | | ABOVE FINISHED FLOOR. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|