2012-07-23 14:35:49FBC PLUMBING REVIEW #1
 DENIED:
  
 1. NO DRINKING FOUNTAIN WAS FOUND ON THE PLANS.
 BUSINESS OCCUPANCIES WITH OVER 15 OCCUPANTS REQUIRE
 DRINKING FOUNTAINS THAT MEET TABLE 403.1 AND THE
 FLORIDA ACCESSIBILITY CODE
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
 ***NOTE***:
 PLEASE SHOW LOCATION OF DRINKING FOUNTAIN IF ONE EXISTS
 ALREADY FOR THIS FLOOR.
  
 2. NO DETAIL WAS FOUND FOR THE LOUNGE SINK.
 FBC ACCESSIBILITY 602.2 CLEAR FLOOR SPACE COMPLYING
 WITH 305 & 306 OR EXCEPTION #1 SIDE APPROACH WITH SINK
 CENTERED A MINIMUM OF 24" FROM SIDE WALL IS REQUIRED.
 606.3 COUNTER TOP OR SINK RIM SHALL BE A MAXIMUM OF 34"
 ABOVE FINISHED FLOOR.
  