| Date |
Text |
| 2012-07-17 09:57:03 | 2505 NORTH DIXIE HIGHWAY |
| | PERMIT #12070380 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THIS PERMIT SHOULD BE A PROPOSED CHANGE IN OCCUPANCY |
| | FROM MERCANTILE (MARKET ) TO ASSEMBLY (RESTAURANT). |
| | |
| | THE SEATING AREA IS APPROXIMATELY 1,050 SQUARE FEET |
| | WHICH EQUATES TO AN OCCUPANT LOAD OF 70 PERSONS BASED |
| | UPON AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON |
| | USING TABLES/CHAIRS. |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | AN ASSEMBLY OCCUPANCY WILL REQUIRE TWO SEPARATE EXITS. |
| | |
| | THE PLANS INDICATE THIS BUILDING IS PROTECTED BY AN |
| | AUTOMATIC SPRINKLER SYSTEM. PLEASE CONFIRM AS OUR |
| | RECORDS DO NOT SHOW SPRINKLERS IN THIS BUILDING. |
| | |
| | A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY |
| | DOOR; HOWEVER, THE MAIN ENTRY IS PERMITTED TO BE |
| | EQUIPPED PANIC HARDWARE OR WITH A KEYED LOCK WITH |
| | LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE |
| | DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO |
| | OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. |
| | |
| | SEPARATE PLANS AN PERMITS NEEDED FOR KITCHEN EXHAUST |
| | HOOD AND HOOD SUPPRESSION SYSTEM. |
| | |
| | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| | TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE |
| | SURFACE. |
| | |
| | PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF SPACE |
| | BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE |
| | ADJACENT EQUIPMENT. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |