| 2012-08-14 10:00:00 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THIS STRUCTURE IS LOCATED WITHIN 600 FEET OF THE |
| | INTER-COASTAL WATERWAY. ACCORDING TO FBCR 301.2.1.4.3, |
| | THE EXPOSURE CATEGORY FOR THIS PROJECT IS 'D'. PLEASE |
| | CORRECT. |
| | |
| | 2) PLEASE REVISE THE COMPONENT AND CLADDING PRESSURES |
| | LISTED ON SHEETS A-1 AND A-3 TO BE CONSISTENT WITH |
| | EXPOSURE CATEGORY D. FBCR301.2.1 |
| | |
| | 3) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA (SFHA), SPECIFICALLY AN A5 FLOOD ZONE. THE MINIMUM |
| | FINISH FLOOR HEIGHT REQUIRED BY THE CITY OF WPB FLOOD |
| | ORDINANCE IS 7.5' ABOVE BASE FLOOD ELEVATION (BFE). |
| | THIS INCLUDES THE 6" FREEBOARD THAT HAS BEEN ADOPTED BY |
| | THE CITY. PLEASE SPECIFY THE FINISH FLOOR ELEVATION ON |
| | THE PLANS AND SUBMIT AN ELEVATION CERTIFICATE FOR THE |
| | PROPOSED ENCLOSED FOYER ADDITION. WPB CITY ORDINANCES |
| | CHAPTER 94 ARTICLE XVII SEC. 94-541 THROUGH 94-547. |
| | |
| | 4) THE SURVEY THAT WAS SUBMITTED INDICATES THAT THE |
| | STRUCTURE APPEARS TO LIE IN FLOOD ZONE "B" . HOWEVER, |
| | THE STRUCTURE IS LOCATED IN FLOOD ZONE "A5". PLEASE |
| | SUBMIT CORRECTED SURVEY. CITY AMENDMENTS 107.2.1 |
| | |
| | 5) SUBMIT TWO COPIES FOR PRODUCT APPROVALS FOR THE NEW |
| | DOOR, ROOF SHINGLES AND SIMPSON CONNECTORS AS REQUIRED |
| | BY DCA RULE 9N-3. |
| | |
| | 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT PER CITY AMENDMENTS 107.3.4.1. |
| | |
| | 7) FBC R 403.1.4 REQUIRES ALL EXTERIOR FOOTINGS TO BE A |
| | MINIMUM OF 12" BELOW GRADE. SECTION 1 ON SHEET A-3 |
| | INDICATES THE FOOTING 10" BELOW GRADE. PLEASE REVISE. |
| | |
| | 8) SECTION 2 ON A-3 SHOWS THE 8" X 16" FOOTING WITH 2 |
| | #5S, HOWEVER, IT IS MISLABELED AS THE 8" X 8" FOOTING |
| | W/1 #5. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |