| Plan Review Notes For Permit 12070357 |
| Permit Number |
12070357 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-22 13:20:56 | 2010 FBC | | | | | | DENIED BY GAS | | | | | | 1) SUBMIT TWO COPIES OF A GAS RISER DIAGRAM. SPECIFY | | | THE TYPES OF PIPE, THE PIPE SIZES, THE PIPE LENGTHS, | | | THE BTUS OF THE EQUIPMENT AND THE GAS PIPE SIZING | | | TABLES OR SIZING EQUATIONS USED. FBCR G2413.1 | | | | | | 2) SHOW COMPLIANCE WITH FBCR G2415.4 (404.4) REQUIRES | | | GAS PIPING TO ENTER AND EXIT A BUILDING AT A POINT | | | ABOVE GRADE. | | | | | | 3) THIS INFORMATION CAN BE PROVIDED NOW OR UNDER A | | | SEPARATE GAS PERMIT WITH SEPARATE APPLICATION AND | | | REVIEW AT A LATER DATE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|