| Plan Review Notes For Permit 12070357 |
| Permit Number |
12070357 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-24 14:04:11 | 12070357 | | | 231 PLYMOUTH ROAD | | | NEW SFD | | | | | | PLEASE CLARIFY THE FOLLOWING ITEMS: | | | PROVIDE INTERCONNECTED SMOKE ALARMS AND A CARBON | | | MONOXIDE DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR | | | SLEEPING. SMOKE ALARMS ARE REQUIRED WITHIN AND OUTSIDE | | | EACH SLEEPING AREA. 2010 FBC R314, 315 | | | RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | PROVIDE LOCATION OF PANEL BOARD. NEC 215.5, 110.26 | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. 2008 NEC 250.94 | | | PROVIDE A NOTE THAT THE LETTER ?G? REPRESENTS A GROUND | | | FAULT PROTECTED OUTLET. NEC 210.8 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|