2012-07-24 14:04:1112070357
 231 PLYMOUTH ROAD
 NEW SFD
  
 PLEASE CLARIFY THE FOLLOWING ITEMS:
 PROVIDE INTERCONNECTED SMOKE ALARMS AND A CARBON
 MONOXIDE DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR
 SLEEPING. SMOKE ALARMS ARE REQUIRED WITHIN AND OUTSIDE
 EACH SLEEPING AREA. 2010 FBC R314, 315
 RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 PROVIDE LOCATION OF PANEL BOARD. NEC 215.5, 110.26
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 PROVIDE A NOTE THAT THE LETTER ?G? REPRESENTS A GROUND
 FAULT PROTECTED OUTLET. NEC 210.8
  