Plan Review Notes
Plan Review Notes For Permit 12070357
Permit Number 12070357
Review Stop B
Sequence Number 1
Notes
Date Text
2012-08-29 06:53:222010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE NEW
 DWELLING IN ACCORDANCE WITH FBC ENERGY CONSERVATION
 SECTION 401.2.
  
 2) SHOW COMPLIANCE WITH FBCR G2407.5 FOR INDOOR
 COMBUSTION AIR FOR THE CLOTHES DRYER IN THE UTILITY
 ROOM.
  
 3) PROVIDE STRUCTURAL DETAILS OF THE ARCH OPENINGS.
 CITY AMENDMENTS 107.2.1.3
  
 4) SUBMIT TWO SETS OF A SURFACE WATER DRAINAGE PLAN
 SHOWING COMPLIANCE WITH FBC R401.3.
  
 5) SPECIFY THE UPLIFT LOADS AND ROOF TO WALL CONNECTORS
 ON THE ROOF FRAMING PLAN. FBC R802.1.6.5
  
 6) SUBMIT A FOUNDATION PLAN SHOWING FOOTING SIZES,
 REINFORCEMENT, LOCATIONS, SLAB REINFORCING AND LOCATION
 OF VERTICAL REINFORCEMENT. CITY AMENDMENTS 107.2.1.3
 AND R401.2
  
 7) PROVIDE A STRUCTURAL DETAIL OF THE VERTICAL
 REINFORCEMENT AND HORIZONTAL CAP REINFORCEMENT OF THE
 PARAPET WALL ON THE GARAGE. FBC R606.2.4
  
 8) PROVIDE SCUPPER SIZING CALCULATIONS FOR THE GARAGE
 ROOF. SPECIFY THE SIZES AND LOCATIONS OF THE GARAGE
 ROOF SCUPPERS AND OVERFLOW SCUPPERS. FBCR 903.4 AND FBC
 PLUMBING SECTIONS 1106 AND 1107.
  
 9) THE BEDROOM AND LIBRARY WINDOWS ARE REQUIRED TO
 COMPLY WITH FBCR 310.1 FOR EMERGENCY ESCAPE AND RESCUE
 OPENINGS.
  
 10) SHOW COMPLIANCE WITH FBC R302.5.1 FOR THE DOOR
 BETWEEN THE GARAGE AND THE RESIDENCE.
  
 11) PROVIDE A DETAIL OF HOW THE LOWER ROOF WILL BE
 ATTACHED TO THE WALL OF THE TWO STORY PORTION OF THE
 STRUCTURE. CITY AMENDMENTS 107.2.1.3
  
 12) PROVIDE A DETAIL OF THE STAIRS, INCLUDING THE
 GUARDS AND HANDRAILS. FBCR 311.7 AND 312
  
 13) SPECIFY THE SPACING OF THE ANCHOR BOLTS AT THE TOP
 OF THE MASONRY WALLS SHOWN ON DETAIL 4 ON SHEET A104.
 CITY AMENDMENTS 107.2.1.3
  
 14) ON DETAIL 4 SHEET A104 THE ANCHOR BOLTS ARE SHOWN
 AT THE BASE OF THE MASONRY WALL WHERE THE DOWEL BARS
 FOR THE MASONRY BARS ARE NORMALLY LOCATED. PLEASE
 CLARIFY. CITY AMENDMENTS 107.2.1
  
 15) ON DETAIL 4 SHEET A104 THE CONNECTION OF THE STUDS
 TO THE TOP PLATE AT THE TOP OF THE SECOND FLOOR FRAME
 WALL IS NOT SHOWN. ALSO THE CONNECTOR IDS THAT ARE
 SPECIFIED IN THE DETAIL WHEN LOOKED UP IN THE 2011/2012
 SIMPSON CATALOG DON'T LOOK LIKE THE ONES SHOWN ON THE
 DRAWING. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1.3
  
 16) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION. FBCR 316
  
 17) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT.
 CITY AMENDMENTS 107.3.4.1
  
 18) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9N-3 FOR THE ROOFING MATERIALS FOR THE
 GARAGE FLAT ROOF AND THE BALCONY WATER PROOFING SYSTEM.
  
 19) SUBMIT PRODUCT APPROVALS ( FLORIDA OR MIAMI-DADE )
 AS REQUIRED BY DCA RULE 9N-3 FOR THE EXTERIOR DOORS (
 #S 101, 104, 105 ) , THE SIDELIGHTS AND THE DOUBLE HUNG
 WINDOWS.
  
 20) SUBMIT TWO COPIES OF THE COMPLETE PRODUCT APPROVAL
 WITH THE FL# OR NOA # FOR THE STORM PANELS AS REQUIRED
 BY DCA RULE 9N-3.
  
 21) SUBMIT TWO COPIES OF AN INSTALLATION SCHEDULE AND A
 KEY PLAN FOR THE OPENINGS THAT WILL HAVE THE STORM
 PANELS. SPECIFY THE ANCHOR TYPE AND SPACING AND OTHER
 REQUIRED CRITERIA LISTED IN THE STORM PANEL PRODUCT
 APPROVAL THAT WILL BE REQUIRED FOR INSTALLATION. CITY
 AMENDMENTS 107.2.1.3
  
 22) SPECIFY THE METHOD OF ATTACHMENT LISTED IN THE ROOF
 TILE PRODUCT APPROVAL THAT WILL BE USED. IF AN ADHESIVE
 IS USED SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR
 IT. DCA RULE 9N-3 AND FBC R905.3.7
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]