| Plan Review Notes For Permit 12070329 |
| Permit Number |
12070329 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-17 10:37:31 | FBC FUEL GAS 2010 REVIEW #1 | | | DENIED: | | | | | | 1. THE ORIGINAL PLAN FOR THE POOL HEATER #12020448 | | | SHOWS 1 1/4" CSST AT 78' TOTAL LENGTH. THE NEW PLAN | | | ADDING A GENERATOR WOULD BE UNDERSIZED. TOTAL LENGTH | | | WOULD BE 127' AT 693 TOTAL BTU (400 HEATER + 293 | | | GENERATOR). AT LESS THAN 2LB THE REQUIRED SIZE FOR THE | | | MAIN FROM THE METER WOULD BE 2" ON TABLE 402.4(2) & | | | 402.4(13). THE RUN FROM THE POOL HEATER TO THE | | | GENERATOR WOULD BE OK. AS AN ALTERNATE THE SYSTEM COULD | | | BE CHANGED TO 2LB WITH REGULATORS. | | | | | | 2. ***NOTE*** | | | THE GAS PERMIT WILL NOT BE PRINTED BEFORE THE GEN-ELECT | | | PERMIT IS APPROVED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|