| 2012-08-17 13:23:49 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE | | | CLAIMING THE CEILING FAN AND WHOLE HOUSE FAN CREDIT | | | OPTIONS. THE PLANS DO NOT SHOW THE REQUIREMENTS NEEDED | | | TO CLAIM THESE CREDITS. PLEASE SHOW HOW THE | | | REQUIREMENTS WILL BE MET OR REVISE THE ENERGY CALCS. | | | FBC ENERGY CONSERVATION SECTION 405.6 | | | | | | 2) ON SHEET M.1, THE DUCT SUPPLYING AIR TO THE 10 X 10 | | | GRILL IN THE GREAT ROOM IS NOT SHOWN. SPECIFY THE SIZE | | | AND LOCATION OF THE DUCT THAT IS SUPPLYING AIR TO THIS | | | GRILL. CITY AMENDMENTS 107.2.1 AND FBCR M1601.1 | | | (PREVIOUS COMMENT THAT WAS NOT ADDRESSED) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|