2012-08-17 13:23:492010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE
 CLAIMING THE CEILING FAN AND WHOLE HOUSE FAN CREDIT
 OPTIONS. THE PLANS DO NOT SHOW THE REQUIREMENTS NEEDED
 TO CLAIM THESE CREDITS. PLEASE SHOW HOW THE
 REQUIREMENTS WILL BE MET OR REVISE THE ENERGY CALCS.
 FBC ENERGY CONSERVATION SECTION 405.6
  
 2) ON SHEET M.1, THE DUCT SUPPLYING AIR TO THE 10 X 10
 GRILL IN THE GREAT ROOM IS NOT SHOWN. SPECIFY THE SIZE
 AND LOCATION OF THE DUCT THAT IS SUPPLYING AIR TO THIS
 GRILL. CITY AMENDMENTS 107.2.1 AND FBCR M1601.1
 (PREVIOUS COMMENT THAT WAS NOT ADDRESSED)
  