| Plan Review Notes For Permit 12070303 |
| Permit Number |
12070303 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-08-17 15:52:00 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ELEVATION CERTIFICATE CONTAINS SEVERAL MISTAKES. | | | THE BUILDING'S OWNER IS INCORRECT ON THE FORM. THE PLAT | | | NUMBER SHOULD BE 2, INSTEAD OF 3. THE LATITUDE AND | | | LONGITUDE ARE INCORRECT. THE FLOOD ZONE IS A5. SUBMIT | | | TWO COPIES OF THE CORRECTED ELEVATION CERTIFICATES WITH | | | THE SURVEYOR'S ORIGINAL SIGNATURE ON THEM AS REQUIRED | | | BY FS 472.025. | | | | | | 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | ARCH SERIES 2500 ALUMINUM SINGLE HUNG WINDOWS HAS BEEN | | | SUPERSEDED. THE CURRENT PRODUCT APPROVAL FOR THIS | | | WINDOW IS NOA NO. 12-0118.18. PLEASE SUBMIT TWO COPIES | | | OF THE CURRENT NOA THAT HAVE BEEN REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND CITY | | | AMENDMENTS 107.3.4.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|