| Plan Review Notes For Permit 12070243 |
| Permit Number |
12070243 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-16 14:21:56 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. INCLUDE WIND SPEED ON PLAN, FBC RESIDENTIAL 301.2.1. | | | | | | 2. SOME ITEMS WERE OBSCURED WITH WHITE OUT. INCORPORATE | | | CHANGES INTO THE SIGNED AND SEALED PLAN, CANNOT ALTER | | | THE ENGINEER'S SPECIFICATION/DESIGN, FS471. | | | | | | 3. SHOW DIRECTION OF DRAINAGE ON THE SITE PLAN FBC | | | 401.3. | | | | | | 4. SHOW LOCATION OF ATTIC ACCESS, FBC R 807. | | | | | | 5. R802.1.6.3, THE "WALL BRACING GABLE END" DOES NOT | | | SHOW ANY LATERAL SUPPORT, NOT CLEAR HOW THIS DETAIL | | | PROVIDES THE SUPPORT REQUIRED TO RESIST WIND LOADS AND | | | TO PROVIDE BRACING REQUIRED BY FBC RESIDENTIAL 609.4. | | | | | | 6. REVISE "WALL BRACING GABLE END" DETAIL TO INCLUDE | | | GABLE OVERHANG, FBC R 609.4. | | | | | | 7. FBC R 703.6.3, BOND BREAK REQUIRED FOR STUCCO. | | | | | | 8. FBC R 704 EXCEPTION 1, 5/8" STUCCO TOO THICK; REVISE | | | WALL DETAIL TO PROVIDE FOR INSPECTION FOR TERMITES. | | | | | | | | | |
|