| Plan Review Notes For Permit 12070227 |
| Permit Number |
12070227 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-13 13:34:54 | 12070227 | | | 219 CLEMATIS ST. | | | ELECTRIC SERVICE MODIFICATION | | | | | | PLEASE HAVE THE ELECTRICAL ENGINEER ADDRESS THE | | | FOLLOWING REVIEW COMMENTS. PLEASE CALL IF THERE ARE ANY | | | QUESTIONS: | | | | | | ELECTRICAL DESIGN FOR SERVICE EQUIPMENT RATED AT 1200 | | | AMPERES REQUIRES A FLORIDA REGISTERED ENGINEER. 2010 | | | FBC 105.3.1.2 (5), FS CHAPTER 471.003 (2) (H) 2.A | | | | | | VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING | | | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. | | | NEC 230.2, 230.71, 230.72 | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC | | | 110.9, 110.10 | | | | | | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING | | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | | PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. | | | NEC 110.26, 240.24, 408.17 | | | | | | PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|