2012-07-13 13:34:5412070227
 219 CLEMATIS ST.
 ELECTRIC SERVICE MODIFICATION
  
 PLEASE HAVE THE ELECTRICAL ENGINEER ADDRESS THE
 FOLLOWING REVIEW COMMENTS. PLEASE CALL IF THERE ARE ANY
 QUESTIONS:
  
 ELECTRICAL DESIGN FOR SERVICE EQUIPMENT RATED AT 1200
 AMPERES REQUIRES A FLORIDA REGISTERED ENGINEER. 2010
 FBC 105.3.1.2 (5), FS CHAPTER 471.003 (2) (H) 2.A
  
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC
 110.9, 110.10
  
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24, 408.17
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31
  