| 2012-07-21 17:25:40 | 6651 NORTH JOG ROAD | | | PERMIT #12070200 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | UPLOADED SHEETS IDENTIFIED AS (700-C6-008) AND | | | (700-C6-009) ARE BOTH THE SOUTHWEST QUADRANT. UPLOADED | | | SHEET (700-C6-008) IS IDENTIFIED IN THE DRAWING | | | TITLEBLOCK AS (700-C6-009). NOTE: A NORTHWEST QUADRANT | | | SHEET WAS NOT SUBMITTED. | | | | | | ALL FIRE PROTECTION PIPING SHALL BE HYDROSTATICALLY | | | TESTED AT 235 PSI (MINIMUM) FOR 2 HOURS DUE TO THE | | | CHURN PRESSURE OF THE FIRE PUMP(S). | | | | | | PROTECT FIRE HYDRANTS FROM VEHICULAR DAMAGE. HYDRANTS | | | SHALL BE PROVIDED WITH WORKING CLEARANCES OF 7'-6" TO | | | THE FRONT/SIDES AND 4'-0" TO THE REAR. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | TELE: (561) 805-6730 | | | EMAIL: [email protected] | | | |
|