 PERMIT #12070200
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPLOADED SHEETS IDENTIFIED AS (700-C6-008) AND
 (700-C6-009) ARE BOTH THE SOUTHWEST QUADRANT. UPLOADED
 SHEET (700-C6-008) IS IDENTIFIED IN THE DRAWING
 TITLEBLOCK AS (700-C6-009). NOTE: A NORTHWEST QUADRANT
 SHEET WAS NOT SUBMITTED.
  
 ALL FIRE PROTECTION PIPING SHALL BE HYDROSTATICALLY
 TESTED AT 235 PSI (MINIMUM) FOR 2 HOURS DUE TO THE
 CHURN PRESSURE OF THE FIRE PUMP(S).
  
 PROTECT FIRE HYDRANTS FROM VEHICULAR DAMAGE. HYDRANTS
 SHALL BE PROVIDED WITH WORKING CLEARANCES OF 7'-6" TO
 THE FRONT/SIDES AND 4'-0" TO THE REAR.
  