| 2012-07-06 16:11:27 | PROVIDE LISTING FROM A NATIONALLY RECOGNIZED TESTING | | | LAB FOR THE NEW ELECTRIC CONTROL CABINET. NEC 110.3 | | | PROVIDE ENGINEERED DRAWINGS FOR THE MODIFICATIONS TO | | | THE LIFT STATION. NEC 110.3 | | | CLASSIFY THE LOCATION AS TO THE LEVEL OF HAZARD DUE TO | | | FLAMMABLE GASES OR VAPORS OR LIQUIDS. NEC 501.1 | | | PROVIDE CONDUIT SEALS. NEC 501.15 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|