| Plan Review Notes For Permit 12070099 |
| Permit Number |
12070099 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-10-15 14:48:07 | REVISION REQUIRED | | | | | | SUBMIT RAS 117 CALCULATIONS FOR THE TAMKO MODIFIED ROOF | | | SYSTEM NOA NO.12-0227.18. THE ONES THAT WERE SUBMITTED | | | ARE NOT CORRECT FOR A STRUCTURE LOCATED IN A 170 MPH | | | VULT / 132 VASD EXPOSURE D WITH A 22' MEAN ROOF HEIGHT. | | | SUBMIT TWO CORRECTED SETS OF RAS 117 CALCULATIONS. |
|