| Plan Review Notes For Permit 12070099 |
| Permit Number |
12070099 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-09-20 10:53:16 | DENIED BY BUILDING | | | | | | 1) RAS 117 CALCULATIONS ARE INCORRECT. THE SPECIFIED C | | | & C PRESSURES ARE NOT FOR EXPOSURE D. THE ASSEMBLY | | | SPECIFIED ON PAGE 6 OF THE NOA NO. 12-0227.18 IS FOR AN | | | INSULATED WOOD DECK. THE UPLIFT OF 60 PSF THAT IS | | | SPECIFIED IN THE RAS CALCS. DOES NOT MATCH THE SPACING | | | IN THE CALCS. AND IS FOR DEKFAST FASTENERS WITH HEX | | | PLATES. THE CALCS. REFERENCE A SECTION FROM THE 2004 | | | FBC. DCA RULE 9N-3 | | | | | | 2) ENERGY CALCULATIONS ARE NOT SIGNED BY THE | | | OWNER/AGENT AS REQUIRED BY 2010 FBC ENERGY CONSERVATION | | | 405.4. | | | | | | 3) THE NOC WILL NEED TO BE RE-RECORDED PRIOR TO FIRST | | | INSPECTION. FS 713 | | | | | | 4) THE PLANS ARE REQUIRED TO BE REVIEWED BY PALM BEACH | | | COUNTY FOR IMPACT FEES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|