2012-08-07 10:57:292010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED WITHIN 600 FT OF THE
 INTERCOASTAL WATERWAY. ACCORDING TO FBC R301.2.1.4.3,
 THIS STRUCTURE IS LOCATED IN EXPOSURE CATEGORY D.
 PLEASE REVISE THE PRESSURES, UPLIFTS AND OTHER WIND
 LOADS ON THE PLANS.
  
 2) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE ON
 THE OLD 2007 FBC FORM. THE 2010 FBC ENERGY CONSERVATION
 REQUIRES FORM 405. PLEASE SUBMIT 2 SETS OF ENERGY
 CALCULATIONS ON THE PROPER FORMS AS REQUIRED BY FBC
 ENERGY CONSERVATION SECTION 405.4.2.
  
 3) THERE WERE SEVERAL ERRORS ON THE ENERGY CALCULATIONS
 THAT WERE SUBMITTED AS FOLLOWS: 1) THE ADDITION IS ON A
 SLAB FOUNDATION, NOT A CRAWL SPACE. (2) THE CEILING FAN
 CREDIT IS NO LONGER ALLOWED. (3) THE CALCS. SHOW A
 VENTED ATTIC AND SHEET S-2 OF THE PLANS SHOWS AN
 UN-VENTED ATTIC WITH R-30 ICYNENE SPRAY FOAM
 INSULATION. (3) THE RESIDENCE IS LOCATED IN WEST PALM
 BEACH AND THE CALCS. HAVE FORT LAUDERDALE. PLEASE
 REVIEW THE ENERGY CALCULATIONS TO INSURE THAT THE
 INFORMATION GIVEN IS CORRECT. 2010 FBC ENERGY
 CONSERVATION CHAPTER 4.
  
 4) SUBMIT A SIGNED AND SEALED COPY OF THE SOIL REPORT
 AS REQUIRED BY FS 471.025.
  
 5) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SECTIONAL GARAGE DOORS IS EXPIRED. SUBMIT CURRENT
 PRODUCT APPROVALS FOR THE GARAGE DOORS. DCA RULE 9N-3.
  
 6) ROOF NOTE 1 ON SHEET S-6 THAT SPECIFIES THE WIND
 SPEED AS 140MPH 3 SECOND GUST AND EXPOSURE B IS
 INCORRECT. UNDER THE 2010 FBCR THE WINDSPEED FOR WEST
 PALM BEACH IS 170 MPH VULT AND THE EXPOSURE CATEGORY
 FOR THIS STRUCTURE IS D. PLEASE CORRECT. FBC R301.2.1 &
 R301.2.1.4
  
 7) THE COMPONENT AND CLADDING PRESSURES FROM THE FRENCH
 DOOR AND CASEMENT WINDOW PRODUCT APPROVALS ARE LESS
 THAN THE REQUIRED PRESSURES SPECIFIED IN THE TABLE ON
 A-2 FOR MARK C. PLEASE PROVIDE PRODUCT APPROVALS WITH
 ADEQUATE DESIGN PRESSURES AS REQUIRED BY FBC R301.2.1.
 ALSO PLEASE HAVE THE STRUCTURAL ENGINEER REVIEW THE
 COMPONENT AND CLADDING PRESSURES IN THE TABLES ON A-2,
 THEY APPEAR TO BE THE VULT VALUES RATHER THAN THE VASD
 VALUES.
  
 8) ON THE TAMKO PRODUCT APPROVALS FOR THE FLAT ROOF,
 PLEASE SPECIFY THE APPROVED ASSEMBLY AND FASTENING
 OPTION THAT WILL BE USED. ALSO, PROVIDE TWO COPIES OF
 THE ENHANCED FASTENING REQUIREMENTS FOR THE PERIMETER
 AND CORNER AREAS IN ACCORDANCE WITH LIMITATION NUMBER 7
 ON PAGE 15 OF THE PRODUCT APPROVAL.
  
 9) PLEASE SPECIFY THE ATTACHMENT METHOD LISTED IN THE
 PRODUCT APPROVAL THAT WILL BE USED TO INSTALL THE CLAY
 BARREL AND PROVIDE ADEQUATE RESISTANCE TO OVERTURNING
 MOMENT PER FBC R905.3. IF POLYFOAM WILL BE USED PLEASE
 SUBMIT TWO COPIES OF THE PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]