| Plan Review Notes For Permit 12060874 |
| Permit Number |
12060874 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-07-24 09:26:24 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PLEASE SEE ANCHOR SCHEDULES ON SHEET 7. BASED ON THE | | | DETAILS CIRCLED AND THE INSTALLATION SCHEDULE PROVIDED, | | | IT APPEARS THAT BY CONNECTION TYPE "1" YOU PROPOSE TO | | | USE C3 (SEE DETAIL ON SHEET 4) AND FOR "11", C4 IS | | | PROPOSED. | | | | | | FOR -66.5PSF DESIGN PRESSURE, YOU MUST USE THE 73PSF | | | ROW. C1, 57PSF SPACING OF 12" WAS CIRCLED AND INDICATED | | | ON THE INSTALLATION SCHEDULE. HOWEVER, BASED ON THE | | | DETAILS CIRCLED, THIS IS NOT THE CORRECT CONNECTION | | | TYPE. | | | | | | 12" IS OK FOR C3 UP TO 6", BUT SPANS OVER 6' REQUIRE | | | TIGHTER SPACING, SEE ANCHOR SCHEDULES. | | | | | | C4, 73PSF, 12" SPACING DOES NOT COMPLY; 8.5" REQUIRED | | | FOR SPAN UP TO 6'. | | | | | | PLEASE REVISE INSTALLATION SCHEDULE ACCORDINGLY TO SHOW | | | COMPLIANCE WITH FBC 301.1, RESISTANCE TO WIND LOADS. | | | |
|