Plan Review Notes
Plan Review Notes For Permit 12060874
Permit Number 12060874
Review Stop B
Sequence Number 2
Notes
Date Text
2012-07-24 09:26:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PLEASE SEE ANCHOR SCHEDULES ON SHEET 7. BASED ON THE
 DETAILS CIRCLED AND THE INSTALLATION SCHEDULE PROVIDED,
 IT APPEARS THAT BY CONNECTION TYPE "1" YOU PROPOSE TO
 USE C3 (SEE DETAIL ON SHEET 4) AND FOR "11", C4 IS
 PROPOSED.
  
 FOR -66.5PSF DESIGN PRESSURE, YOU MUST USE THE 73PSF
 ROW. C1, 57PSF SPACING OF 12" WAS CIRCLED AND INDICATED
 ON THE INSTALLATION SCHEDULE. HOWEVER, BASED ON THE
 DETAILS CIRCLED, THIS IS NOT THE CORRECT CONNECTION
 TYPE.
  
 12" IS OK FOR C3 UP TO 6", BUT SPANS OVER 6' REQUIRE
 TIGHTER SPACING, SEE ANCHOR SCHEDULES.
  
 C4, 73PSF, 12" SPACING DOES NOT COMPLY; 8.5" REQUIRED
 FOR SPAN UP TO 6'.
  
 PLEASE REVISE INSTALLATION SCHEDULE ACCORDINGLY TO SHOW
 COMPLIANCE WITH FBC 301.1, RESISTANCE TO WIND LOADS.
  