| Plan Review Notes For Permit 12060867 |
| Permit Number |
12060867 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-18 08:31:37 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE | | | ADDITION AS REQUIRED BY THE 2010 FBC ENERGY | | | CONSERVATION SECTION 401.2. | | | | | | 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | | FOR THE HEATING AND COOLING EQUIPMENT AS REQUIRED BY | | | FBCR M1401.3. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|