| Date |
Text |
| 2012-07-18 09:00:56 | DENIED BY BUILDING |
| | |
| | 1) SHOW COMPLIANCE WITH FBC R806.1 FOR REQUIRED ROOF |
| | VENTILATION. |
| | |
| | 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS THAT HAVE |
| | BEEN SIGNED BY THE PREPARER AND THE OWNER AGENT AS |
| | REQUIRED BY FBC ENERGY CONSERVATION SECTION 401.2. |
| | |
| | 3) SPECIFY THE SIZES OF THE ROOF SCUPPERS AND OVERFLOW |
| | SCUPPERS ON SHEET S.01 OF THE PLANS. FBC R903.4.1 AND |
| | FBC PLUMBING 1106.7 AND 1107.3 |
| | |
| | 4) THE COMPONENT AND CLADDING PRESSURES ON SHEET S.01 |
| | IS SPECIFIED AS + / - 64 PSF WORST CASE AND A 6 FEET |
| | MINIMUM EDGE STRIP. HOWEVER, THE DIAGRAM AND ANOTHER |
| | LOCATION SPECIFIES EDGE ZONE PRESSURES AS + 49.42 PSF |
| | AND - 66.08 PSF. THE PRODUCT APPROVAL DESIGN PRESSURES |
| | FOR THE DOORS AND WINDOWS ARE + 55 PSF AND - 65 PSF. |
| | THE + 64 PSF FROM THE FIRST AND THE - 66.08 PSF EXCEEDS |
| | THE DESIGN PRESSURES OF THE PRODUCT APPROVALS. PLEASE |
| | CLARIFY AND PROVIDE THE COMPONENT AND CLADDING |
| | PRESSURES THAT ARE SPECIFIC TO THIS PROJECT. CITY |
| | AMENDMENTS 107.2.1 AND FBC R301.2.1 |
| | |
| | 5) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE CLAY ROOF TILE AND PROVIDE TWO COPIES OF |
| | APPROVALS FOR THE ADHESIVE OR MORTAR PRODUCT THAT WILL |
| | BE USED. FBC R905.3.7 |
| | |
| | 6) SPECIFY THE FASTENING OPTION FROM THE PRODUCT |
| | APPROVAL THAT WILL BE USED TO INSTALL THE GAF MODIFIED |
| | BITUMEN ROOF SYSTEM AND SUBMIT TWO COPIES OF SIGNED AND |
| | SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING AT |
| | THE CORNER AND PERIMETER AREAS AS REQUIRED BY |
| | LIMITATION NUMBER 7 ON PAGE 31 OF THE NOA. FBC R905.11 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |