Plan Review Notes
Plan Review Notes For Permit 12060858
Permit Number 12060858
Review Stop B
Sequence Number 3
Notes
Date Text
2012-11-05 11:16:23BUILDING REVIEW THIRD CHECKLIST:
  
 1- PLANS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT.
 SEC. 107.1 CITY AMENDMENTS TO FBC. PLANS SUBMITTED THIS
 TIME ARE NOT SIGNED AND SEALED.
  
 2- (A) EGRESS WINDOW W2 SPECIFIED ON PLANS DON'T COMPLY
 WITH THE MINIMUM OPENING SIZE REQUIRED BY SEC. R310 OF
 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY
 IF ORDERING CUSTOM SIZE WINDOW. (REPEAT COMMENT. THREE
 TIMES).
  
 ***REVIEW RESPONSE: 37" X 54" SINGLE HUNG WINDOW
 DOESN'T MEET THE EGRESS REQUIREMENTS. I ENTERED WINDOW
 SIZE ON JELD WEN WEBSITE AND THE RESULT IS THAT IT
 DOESN'T MEET THE EGRESS REQUIREMENTS. SEE BELOW.
  
 SINGLE-HUNG
 NET FRAME WIDTH: 37"
 NET FRAME HEIGHT: 54"
 DOES NOT MEET EGRESS REQUIREMENTS.
 CLEAR OPENING WIDTH 34.75 (COMPLIES).
 CLEAR OPENING HEIGHT 20.562 (DOESN'T COMPLY).
 CLEAR OPENING SQ. FT. 4.962 (DOESN'T COMPLY).
  
 (B) THIRD DENIED REVIEW: ARCHITECT TO PAY A FEE OF FOUR
 TIMES THE ATTRIBUTED TO PLAN REVIEW AS REQUIRED BY SEC.
 553.80(2)(B) FLORIDA STATUTE. (SEC. 107.1 CITY
 AMENDMENTS TO FBC).
  
 IMPORTANT NOTICE DESIGN PROFESSIONALS FLORIDA STATUTE
 553.80(2)(B) DESIGN PROFESSIONAL DOCUMENTS:
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION A
 FEE OF FOUR TIMES THE AMOUNT OF THE PORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLAN REVIEW.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS. OWNER SAID NOT
 REPLACING DOOR. THEN, ARCHITECT TO REVISE PLANS
 ACCORDINGLY.
  
 B) CASEMENT WINDOW AS SHOWN ON PLANS. (REPEAT COMMENT.
 NO RESPONSE).
  
 C) SINGLE HUNG WINDOW THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT. NOA 09-0916.05 SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 ***NOTE:
 SUBMIT SEPARATE PERMIT APPLICATIONS FOR ELECTRICAL AND
 FOR MECHANICAL WORK. ONLY PERMIT APPLICATIONS FOR THE
 BUILDING AND PLUMBING WORK WERE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712