Text |
| 2012-07-18 10:24:42 | RESIDENTIAL (R3) GARAGE CHANGE OF USE, PLUMBING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- LOCATION OF VENT TO ROOF SHOWN ON THE PLUMBING RISER | | | DIAGRAM DOESN'T COMPLY WITH SEC. P3108.2.1 OF 2010 | | | FBC-RESIDENTIAL. NO MORE THAN ONE WET-VENTED FIXTURE | | | DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED | | | FIXTURE DRAIN CONNECTION. REVISE AS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|