| 2012-07-18 10:45:46 | RESIDENTIAL (R3) CHANGE OF USE, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.4 AND SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 2- EGRESS WINDOW W2 SPECIFIED ON PLANS DON'T COMPLY |
| | WITH THE MINIMUM OPENING SIZE REQUIRED BY SEC. R310 OF |
| | 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY |
| | IF ORDERING CUSTOM SIZE WINDOW. PGT SIZE CHART DOESN'T |
| | INCLUDE THIS SIZE OF WINDOW. SEE PRODUCT APPROVAL |
| | SUBMITTED. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | SEC. 107.2 CITY AMENDMENTS TO FBC AND RULE 9N-3 FOR: |
| | A) ENTRY DOOR AS SHOWN ON PLANS. |
| | B) CASEMENT WINDOW AS SHOWN ON PLANS. |
| | C) SINGLE HUNG WINDOW. ONLY ONE NOA WAS SUBMITTED. NEED |
| | TWO COPIES. |
| | D) STORM SHUTTERS IF GLASS IN DOORS AND WINDOWS DON'T |
| | HAVE HURRICANE IMPACT GLASS. AND, PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE SHOWING CONNECTION TYPE, ANCHOR |
| | TYPE AND SPACING. |
| | E) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS. |
| | PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR. |
| | |
| | 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 5- ARCHITECT TO REVISE/CLARIFY SPECIFICATIONS SHOWN ON |
| | PLANS. SEC.107.2.1 CITY AMENDMENTS TO FBC: |
| | A) THIS IS NOT ALTERATION LEVEL 1. THIS IS A CHANGE OF |
| | OCCUPANCY FROM GARAGE TO LIVING AREA. SEC. |
| | 406-FBC-EXISTING BUILDING. REVISE AS REQUIRED. |
| | B) ARCHITECT SPECIFIES ALUMINUM IMPACT GLASS PER FBC |
| | 1026.2. THIS SECTION IS NOT RELATED TO IMPACT GLASS. |
| | CITE CORRECT SECTION. SEE 2010 FLORIDA RESIDENTIAL CODE |
| | AND REVISE AS REQUIRED. |
| | C) ARCHITECT SPECIFIES 5.0 SF MIN. OPENING FOR EGRESS |
| | WINDOW @ GRADE PER SEC. 1026.2.1. THIS SECTION IS NOT |
| | RELATED TO WINDOW EGRESS. SEE 2010 FLORIDA RESIDENTIAL |
| | CODE AND REVISE AS REQUIRED. |
| | |
| | 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY BUILDING TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. THIS IS REQUIRED BY THE COUNTY IMPACT FEE |
| | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | |
| | ***NOTE: |
| | SUBMIT SEPARATE PERMIT APPLICATIONS FOR A/C WORK, |
| | ELECTRICAL WORK. ONLY PERMIT APPLICATIONS FOR THE |
| | BUILDING AND PLUMBING WORK WERE SUBMITTED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |