| 2012-07-11 14:08:17 | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 12060801 |
| | ADD: 2480 PRESIDENTIAL WAY # 1002 |
| | CONT: TYCON CONSTRUCTION |
| | TEL: (561)756-1409 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | BUILDING PROVISO: |
| | PLANS DO NOT INDICATE THE REMOVAL OF FLOORING, IF FLOOR |
| | COVERINGS ARE TO BE REMOVED THEN COMPLIANCE WITH : |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1A) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE |
| | MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR |
| | TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND |
| | IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| | 603.1.3.2 EXCEPTIONS: |
| | 1 INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |