| Notes |
| Date |
Text |
| 2012-07-09 09:27:00 | 12060789 | | | 2615 OKEECHOBEE BLVD. | | | NEW COMMERCIAL BLDG. FOR VERIZON | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | NEW SERVICE, SWITCH GEAR AND ELECTRIC PANEL. NEC 110.9, | | | 110.10 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | | EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING | | | THE TYPE OF HAZARD AND MAGNITUDE. 2008 NEC 110.22, | | | 110.16 | | | | | | PROVIDE A DESIGNATED LOCATION FOR THE ELECTRICAL PANEL | | | BOARD WHICH REMAINS CLEAR OF OBSTRUCTION AND STORAGE AT | | | ALL TIMES. NEC 240.24 | | | | | | PROVIDE SIGNED AND SEALED WIND LOADING CERTIFICATION | | | FOR THE SITE LIGHT POLE ASSEMBLY WITH FIXTURES. 2010 | | | FBC 1609.1., ASCE 7-10 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|