Plan Review Notes
Plan Review Notes For Permit 12060760
Permit Number 12060760
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-06-28 14:25:306/28/2012 PLANS REVIEWED BY FIRE ***DENIED***
  
 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
  
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101
  
 3. FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS.
  
 PLANS PLACED IN MISC #3
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  