| Plan Review Notes For Permit 12060751 |
| Permit Number |
12060751 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-12-26 10:45:17 | BUILDING PLAN REVIEW | | | PERMIT: 12060751 | | | ADD: 2020 CHAGAL CIR | | | CONT: ARMENTI CONST. & ACCESS SYST. | | | TEL: (561)386-6826 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | NEW COMMENTS: SHOW COMPLIANCE WITH NEW 2010 CODE | | | SECTIONS : | | | 1A) 3110.3 VEHICULAR GATES INTENDED FOR AUTOMATION. | | | VEHICULAR GATES INTENDED FOR AUTOMATION SHALL BE | | | DESIGNED, CONSTRUCTED AND INSTALLED TO COMPLY WITH THE | | | REQUIREMENTS OF ASTM F 2200. | | | | | | 1B) 3110.4 VEHICULAR GATE OPENERS. | | | VEHICULAR GATE OPENERS, WHEN PROVIDED, SHALL BE LISTED | | | IN ACCORDANCE WITH UL 325. | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|