| Notes |
| Date |
Text |
| 2012-06-27 08:05:31 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | 1. FBC EXISTING BUILDING 701.2, 601.2, AND FBC | | | 709.1(6), 712.3, SHOW REQUIRED FIRE RESISTANCE RATED | | | WALLS AND FLOOR/CEILING AND CEILING/ROOF ASSEMBLIES. IT | | | APPEARS THAT THE DRYWALL BEING REMOVED AND REPLACED IS | | | A PART OF A RATED ASSEMBLY. VERIFY REQUIREMENTS AND | | | PROVIDE DETAILS WHICH SHOW COMPLIANCE WITH ANY FIRE | | | RATING REQUIREMENTS, FBC 703.2. | | | | | | | | | | | | | | | | | | | | | | | | | | | BLD-COM PERMITS IN COMMUNITY PLUS UNDER 3900 N FLAGLER | | | DR | | | | | | TYPE V S CONSTRUCTION | | | | | | 3 LEVELS OVER PARKING | | | | | | |
|