Notes
Date Text
2012-07-12 11:53:57BUILDING PLAN REVIEW
 PERMIT: 12060693
 ADD: 1201 ALLENDALE RD
 CONT: TIM JOHNSON REMODELING
 TEL: (561)707-7058
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2010 FBC/ B WPB ADMINISTRTIVE CODE107.3.5 MINIMUM
 PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED. WHAT TYPE OF OCCUPANCY WILL THE
 MEZZANINE BE USED FOR?
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EMERGENCY LIGHTING AND EXIT SIGNS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY IF THE MEZZANINE LEVEL IS USED
 FOR OTHER THAN STORAGE.
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
  
 2) POSTING OF THE FLOOR LOAD OF THE MEZZANINE PER WPB
 ADMINISTRATIVE CODE.106.1 LIVE LOADS POSTED. WHERE THE
 LIVE LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH DESIGN
 LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE OWNER
 IN THAT PART OF EACH STORY IN WHICH THEY APPLY, USING
 DURABLE SIGNS. IT SHALL BE UNLAWFUL TO REMOVE OR DEFACE
 SUCH NOTICES.
  
 3) THE PLANS DO NOT INDICATE TO WHAT LIVE LOAD THEY
 WERE DESIGNED PLEASE REVIEW 2010FBC-B TABLE 1607.1.
 (35) 100 LBS.
  
 4) PLANS INDICATE THEY ARE DESIGNED TO THE 2007FBC-B,
 MARCH 15/2012 THE 2010 FBC-B WAS ADOPTED STATE WIDE THE
 WIND DESIGN ASCE 7-10, WE ARE LOCATED IN A 170 MPHWIND
 ZONE FOR CATEGORY II BUILDINGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676