| 2012-07-16 13:22:02 | PLANS DENIED | | | 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER | | | TABLE | | | 403.3 2010 FBC (M) | | | 2) DUCT DETECTOR MUST BE INSTALLED IN SUPPLY DUCT | | | PER SECTION 606.2.1 SUPPLY AIR SYSTEM. 2010 FBC (M) | | | 3) SUBMIT HEATING AND COOLING CALCULATIONS WITH PLANS. | | | PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010. | | | 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS. | | | FLORIDA ENERGY CODE 2010 | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|