Date Text
2012-07-16 13:22:02PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE
 403.3 2010 FBC (M)
 2) DUCT DETECTOR MUST BE INSTALLED IN SUPPLY DUCT
 PER SECTION 606.2.1 SUPPLY AIR SYSTEM. 2010 FBC (M)
 3) SUBMIT HEATING AND COOLING CALCULATIONS WITH PLANS.
 PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010.
 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 FLORIDA ENERGY CODE 2010