| 2012-07-03 16:56:47 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- ENERGY CALCULATIONS FORM 1100A-08 SUBMITTED IS FOR | | | 2007 CODE. PROVIDE CURRENT ENERGY CALCULATIONS AS | | | REQUIRED BY SEC. 103.2.1 OF 2010 FBC-ENERGY | | | CONSERVATION. COMPLETE ALL THE INFORMATION ON TOP OF | | | FORM. OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM ALSO. | | | PERSON PREPARING THE CALCULATIONS TO COORDINATE | | | INFORMATION WITH FLOOR PLANS SUBMITTED. THERE ARE NOT | | | SHINGLES ON THIS HOUSE. MAKE SURE ENERGY CALCULATIONS | | | COMPLY WITH THE REQUIREMENTS OF TABLE 402.1.1 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 2- PROVIDE MANUFACTURER SPECIFICATIONS FOR NEW DOORS | | | AND WINDOWS SHOWING COMPLIANCE WITH THE ENERGY | | | EFFICIENCY AS REQUIRED BY THE ENERGY CALCULATIONS AND | | | TABLE 402.1.1 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | SEC. 107.2 OF CITY AMENDMENTS TO FBC FOR: | | | A) EXTERIOR DOORS AS SHOWN ON PLANS. | | | | | | B) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. ONLY ONE COPY | | | WAS SUBMITTED. | | | | | | 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|