Plan Review Notes For Permit 12060665
Permit Number 12060665
Review Stop G
Sequence Number 1
Notes
Date Text
2012-07-03 10:28:04GAS REVISION REVIEW COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- NEED CONTRACTOR TO APPLY FOR SEPARATE GAS PERMIT.
 SEC. 105.1 CITY AMENDMENTS TO FBC. CONTRACTOR TO
 PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT.
 CONTRACTOR TO COORDINATE WITH COMMENT #2 BELOW.
  
 2- ENGINEER TO REVISE THE GAS RISER DIAGRAM. ACCORDING
 TO TABLE G2413.4(5) [402.4(13)] OF THE 2010
 FBC-RESIDENTIAL, THE TUBE SIZE REQUIRED FOR THE STOVE
 OVEN (96 EHD) AND 70 FEET DEVELOPED LENGTH IS 30 OR 31
 (1") FLOW DESIGNATION. NOT 23 (3/4").
  