| Notes |
| Date |
Text |
| 2012-07-03 10:28:04 | GAS REVISION REVIEW COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- NEED CONTRACTOR TO APPLY FOR SEPARATE GAS PERMIT. | | | SEC. 105.1 CITY AMENDMENTS TO FBC. CONTRACTOR TO | | | PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT. | | | CONTRACTOR TO COORDINATE WITH COMMENT #2 BELOW. | | | | | | 2- ENGINEER TO REVISE THE GAS RISER DIAGRAM. ACCORDING | | | TO TABLE G2413.4(5) [402.4(13)] OF THE 2010 | | | FBC-RESIDENTIAL, THE TUBE SIZE REQUIRED FOR THE STOVE | | | OVEN (96 EHD) AND 70 FEET DEVELOPED LENGTH IS 30 OR 31 | | | (1") FLOW DESIGNATION. NOT 23 (3/4"). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATIONS PLANS EXAMINER | | | (561)805-6712 |
|