| 2012-07-16 13:05:31 | BUILDING PLAN REVIEW |
| | PERMIT: 12060646 |
| | ADD: 1200 S FLAGLER DR # 1402 |
| | CONT: SUNRISE CONSTRUCTION |
| | TEL: (772)260-8111 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES NEW FLOORS AND THE |
| | PLANS INDICATE THE USE OF SOUND PROOFING, PLAESE |
| | PROVIDE CODE COMPLIANCE FOR; |
| | |
| | COMPLIED. |
| | |
| | 1B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE |
| | MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR |
| | TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND |
| | IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| | 603.1.3.2 EXCEPTIONS: |
| | 1 INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 7/11/12 RESUBMITTAL FOR USE OF ACCOUSTICORK CONTRACTOR |
| | BROUGHT IN INFORMATION TO MEET 2010 FBC-B 1207.3 |
| | STRUCTURE BORNE SOUND/ THERE IS ALSO A LEGACY REPORT |
| | ER-5314 |
| | CONFIRMING CODE COMPLIANCE. |
| | |
| | STILL MISSING IS THE FLAME SPREAD REQUIREMENTS OF 2010 |
| | FBC-B 603.1.3.2 (1). |
| | INSULATION PLACED BETWEEN TWO LAYERS OF NONCOMBUSTIBLE |
| | MATERIALS WITHOUT AN INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 100. |