Date Text
2012-07-16 13:05:31BUILDING PLAN REVIEW
 PERMIT: 12060646
 ADD: 1200 S FLAGLER DR # 1402
 CONT: SUNRISE CONSTRUCTION
 TEL: (772)260-8111
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES NEW FLOORS AND THE
 PLANS INDICATE THE USE OF SOUND PROOFING, PLAESE
 PROVIDE CODE COMPLIANCE FOR;
  
 COMPLIED.
  
 1B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE
 MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR
 TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND
 IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
 603.1.3.2 EXCEPTIONS:
 1 INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 7/11/12 RESUBMITTAL FOR USE OF ACCOUSTICORK CONTRACTOR
 BROUGHT IN INFORMATION TO MEET 2010 FBC-B 1207.3
 STRUCTURE BORNE SOUND/ THERE IS ALSO A LEGACY REPORT
 ER-5314
 CONFIRMING CODE COMPLIANCE.
  
 STILL MISSING IS THE FLAME SPREAD REQUIREMENTS OF 2010
 FBC-B 603.1.3.2 (1).
 INSULATION PLACED BETWEEN TWO LAYERS OF NONCOMBUSTIBLE
 MATERIALS WITHOUT AN INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 100.