Plan Review Notes
Plan Review Notes For Permit 12060593
Permit Number 12060593
Review Stop B
Sequence Number 2
Notes
Date Text
2012-06-25 10:48:30RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS.
 2010 FBC.
  
 1- ENGINEER TO REVIEW FLAT ROOF NOA 07-1219.09
 SUBMITTED, THEN, REVIEW SPECIFIC APPROVED ASSEMBLY AND
 THEN PROVIDE THE RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA.
 CALCULATIONS SUBMITTED ARE NOT ADDRESSING RAS 117.
  
  
 THE FOLLOWING ARE THE ORIGINAL COMMENTS ON THE FIRST
 CHECKLIST:
  
 1- FLAT ROOF NOA 07-1219.09 SUBMITTED:
 A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FLORIDA
 RESIDENTIAL CODE.
  
 A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED NAIL ENHANCING TO MEET THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3.
  
 2- ACCORDING TO MIAMI-DADE WEBSITE SHINGLES NOA
 07-1012.02 SUBMITTED WAS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA AS REQUIRED BY DCA RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  