| Plan Review Notes For Permit 12060593 |
| Permit Number |
12060593 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-06-25 10:48:30 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | | COMMENTS. | | | 2010 FBC. | | | | | | 1- ENGINEER TO REVIEW FLAT ROOF NOA 07-1219.09 | | | SUBMITTED, THEN, REVIEW SPECIFIC APPROVED ASSEMBLY AND | | | THEN PROVIDE THE RAS 117 CALCULATIONS AS REQUIRED BY | | | GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA. | | | CALCULATIONS SUBMITTED ARE NOT ADDRESSING RAS 117. | | | | | | | | | THE FOLLOWING ARE THE ORIGINAL COMMENTS ON THE FIRST | | | CHECKLIST: | | | | | | 1- FLAT ROOF NOA 07-1219.09 SUBMITTED: | | | A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FLORIDA | | | RESIDENTIAL CODE. | | | | | | A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NEED NAIL ENHANCING TO MEET THE DESIGN | | | PRESSURES OF SEC. R301.2.1.4.3. | | | | | | 2- ACCORDING TO MIAMI-DADE WEBSITE SHINGLES NOA | | | 07-1012.02 SUBMITTED WAS SUPERSEDED. NEED TO PROVIDE | | | CURRENT NOA AS REQUIRED BY DCA RULE 9N-3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|