| 2012-07-09 15:46:54 | BUILDING PLAN REVIEW |
| | PERMIT: 12060539 |
| | ADD: 1801 S FLAGLER # 1602 |
| | CONT: MARYJULE CONSTRUCTION, INC |
| | TEL: (561)386-6032 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET # 1 INDICATES NEW EXTERIOR WINDOWS AND SLIDING |
| | GLASS DOORS. NO PRODUCT TESTING REPORTS WERE SUBMITTED, |
| | NOTED THIS UNIT IS LOCATED ON THE 16TH FLOOR AND WILL |
| | ONLY NEED TO COMPLY FOR WIND. |
| | COMPONENTS & CLADDING 2010 FBC-B 1609.6.4.4.1. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 4) THE PERMIT APPLICATION INDICATES NEW FLOORS AND THE |
| | PLANS INDICATE THE USE OF "EASY MAT" SOUND PROOFING, |
| | PLAESE PROVIDE CODE COMPLIANCE FOR; |
| | 3A) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | 3B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE |
| | MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR |
| | TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND |
| | IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| | 603.1.3.2 EXCEPTIONS: |
| | 1 INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | 5) SHEET 1 INDICATES THE CEILINGS ARE TO BE FURRED DOWN |
| | 3/4" WITH 3/4" FURRING CHANNELS, IS THIS HI-HAT |
| | MATERIAL AND IF SO HOW OFTEN IS THE HI-HAT TO BE |
| | FASTENED AND WITH WHAT TYPE OF FASTENER? ADDITIONAL |
| | INFORMATION REQUIRED 107.2.1.3. |
| | |
| | 6) SHEET 1 INDICATES THE REMOVAL OF TUB AND THE |
| | INSTALATION OF A NEW SHOWER, PLEASE PROVIDE |
| | DOCUMENTATION FOR CODE COMPLIANCE FOR: |
| | 2010 FBC-B 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT |
| | OR GLASS MAT GYPSUM BACKERS IN COMPLIANCE WITH ASTM C |
| | 1178, C 1288 OR C 1325 AND INSTALLED IN ACCORDANCE WITH |
| | MANUFACTURER RECOMMENDATIONS SHALL BE USED AS A BASE |
| | FOR WALL TILE IN TUB AND SHOWER AREAS AND WALL AND |
| | CEILING PANELS IN SHOWER AREAS. WATER-RESISTANT GYPSUM |
| | BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER |
| | CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE |
| | WITH GA-216 OR ASTM C 840 AND MANUFACTURER |
| | RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED |
| | UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING |
| | AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM |
| | C 840. |
| | |
| | 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING |
| | BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS: |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | 2 . WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |