| 2012-08-03 18:14:54 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | DISCUSSED WITH ARCHITECT THE FOLLOWING ISSUES: |
| | |
| | 1. BASED ON SQUARE FOOT AREA PROVIDED AND FBC TABLE |
| | 1004, OCCUPANT LOAD WILL BE OVER 50 (6870 / 30 = 229). |
| | DOORS IN THE MEANS OF EGRESS ARE TO SWING IN THE |
| | DIRECTION OF TRAVEL, BUT AS DISCUSSED EXISTING BUILDING |
| | CODE 101.5 EXCEPTION ALLOWS USE OF CODE IN EFFECT WHEN |
| | THE BUILDING WAS BUILT WITH APPROVAL FROM THE BUILDING |
| | OFFICIAL. |
| | |
| | IT APPEARS FROM THE SURVEY THAT THE DIXIE HIGHWAY DOOR |
| | CAN SWING OUT AND WILL NOT ENCROACH INTO THE PUBLIC |
| | WAY; PLEASE VERIFY, AND AS DISCUSSED, PLEASE |
| | INVESTIGATE THE POSSIBILITY THAT THIS DOOR CAN SWING |
| | OUT. |
| | |
| | THE FLAMINGO DRIVE SIDE OF THE BUILDING IS ON THE |
| | PROPERTY LINE, SO THIS DOOR WOULD NEED TO EITHER HAVE A |
| | VESTIBULE, SWING OUT ENTIRELY OVER THE PROPERTY LINE |
| | AND FULL ENCROACHMENT INTO THE PUBLIC WAY, OR SWING IN. |
| | THE PROPOSED IRON GRILLS ARE SHOWN SWINGING OUT OVER |
| | THE PROPERTY LINE. |
| | |
| | IN THE 1929 BUILDING CODE, SECTION 46 INCLUDES SOME |
| | PROVISION FOR ENCROACHING THE PROPERTY LINE WITH DOORS |
| | WHICH ARE NORMALLY IN THE CLOSED POSITION, BUT ONLY IN |
| | FIRE DISTRICTS 3 AND 4, BUT NOT IN 1 AND 2. IT WOULD |
| | REQUIRE FURTHER INVESTIGATION TO DETERMINE WHICH FIRE |
| | DISTRICT THIS PROPERTY WAS IN AT THAT TIME. |
| | |
| | AS DISCUSSED, THE PRIMARY ENTRANCE AND EXIT DOOR WILL |
| | BE THE REAR DOOR, AND THE AREA ADJACENT TO THIS DOOR |
| | WILL NOT BE USED FOR STORAGE AS THIS IS THE DOOR |
| | LEADING FROM THE PARKING AREA DIRECTLY TO THE BUILDING. |
| | |
| | AS DISCUSSED, PLEASE SUBMIT AN EMAIL WHICH OUTLINES |
| | PROPOSED EXITING STRATEGY, PROPOSED DOOR SWING, AND |
| | EXISTING CONDITIONS TO SUPPORT YOUR REQUEST TO EITHER |
| | HAVE INSWING DOORS, OUTSWING DOOR OR GRILL ENCROACHING |
| | PROPERTY LINE. THIS WILL BE DISCUSSED WITH THE ABO. |
| | |
| | |