| Plan Review Notes For Permit 12060531 |
| Permit Number |
12060531 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-07-06 15:38:32 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | COMPONENTS & CLADDING (DOORS, WINDOWS), 9N-3. | | | | | | 2. DOOR & WINDOW DATA, SHEET A01, REFERS TO THE | | | RESIDENTIAL CODE. FBC 2010 BUILDING SHOULD BE USED FOR | | | THIS COMMERCIAL BUILDING, PLEASE REVISE. | | | | | | 3. DOOR & WINDOW DATA REFERS TO 2ND FLOOR DOORS, PLEASE | | | REMOVE NOTE OR PROVIDE PLAN FOR 2ND FLOOR WORK. | | | | | | 4. PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL | | | DISTANCE, OCCUPANT LOAD, OCCUPANCY CLASSIFICATION FBC | | | 1004 FOR EACH AREA, ROOM DESIGNATIONS FOR ALL AREAS. | | | NOT ENOUGH INFORMATION PROVIDED TO GIVE A COMPLETE | | | COMMENT LIST AS OCCUPANT LOAD IS REQUIRED IN ORDER TO | | | DETERMINE DOOR SWING REQUIREMENTS, ELIMINATION OF EXIT | | | DOOR. BUILDING PLANS ON FILE SHOW A RECESSED OUTSWING | | | DOOR IN THESE LOCATIONS. FBC 1008.1.2. | | | | | | 5. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED SILL, | | | FBC 106, FBC 1609. | | | | | | 6. IF OUTSWING DOORS ARE PROPOSED, PROVIDE A SITE | | | PLAN/SURVEY SHOWING ENCROACHMENT OVER PROPERTY LINE, | | | FBC 3202.2. | | | | | | 7. SEE FBC 2010 EXISTING BUILDING 101.5 AND SELECT | | | METHOD OF COMPLIANCE. | | | | | | |
|