2012-07-06 15:38:32****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 COMPONENTS & CLADDING (DOORS, WINDOWS), 9N-3.
  
 2. DOOR & WINDOW DATA, SHEET A01, REFERS TO THE
 RESIDENTIAL CODE. FBC 2010 BUILDING SHOULD BE USED FOR
 THIS COMMERCIAL BUILDING, PLEASE REVISE.
  
 3. DOOR & WINDOW DATA REFERS TO 2ND FLOOR DOORS, PLEASE
 REMOVE NOTE OR PROVIDE PLAN FOR 2ND FLOOR WORK.
  
 4. PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL
 DISTANCE, OCCUPANT LOAD, OCCUPANCY CLASSIFICATION FBC
 1004 FOR EACH AREA, ROOM DESIGNATIONS FOR ALL AREAS.
 NOT ENOUGH INFORMATION PROVIDED TO GIVE A COMPLETE
 COMMENT LIST AS OCCUPANT LOAD IS REQUIRED IN ORDER TO
 DETERMINE DOOR SWING REQUIREMENTS, ELIMINATION OF EXIT
 DOOR. BUILDING PLANS ON FILE SHOW A RECESSED OUTSWING
 DOOR IN THESE LOCATIONS. FBC 1008.1.2.
  
 5. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED SILL,
 FBC 106, FBC 1609.
  
 6. IF OUTSWING DOORS ARE PROPOSED, PROVIDE A SITE
 PLAN/SURVEY SHOWING ENCROACHMENT OVER PROPERTY LINE,
 FBC 3202.2.
  
 7. SEE FBC 2010 EXISTING BUILDING 101.5 AND SELECT
 METHOD OF COMPLIANCE.
  
  