2012-07-23 09:31:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IN ORDER TO FACILITATE INSPECTIONS AND PLAN REVIEW,
 PLEASE COMPLETE THE INSTALLATION SCHEDULE. ANCHOR
 SPACING, DESIGN PRESSURE COLUMNS WERE LEFT BLANK.
 ANOTHER SHEET STATES THAT THIS PROJECT IS DESIGNED TO
 -66PSF, BUT ANCHOR SPACING PROPOSED DOES NOT COMPLY
 (SEE OTHER COMMENTS). THERE ARE TOO MANY OPENINGS TO
 PROVIDE A GENERIC STATEMENT REGARDING SPACING;
 INSTALLATION PROPOSED IS TO BE REVIEWED FOR COMPLIANCE
 WITH FBC RESIDENTIAL 301.1, RESISTANCE TO WIND LOADS.
  
 2. MANY ITEMS WERE HIGHLIGHTED ON THE PRODUCT APPROVAL;
 MULTIPLE FASTENERS, FASTENING METHODS, DESIGN
 PRESSURES, EDGE DISTANCE, SUBSTRATE. PLEASE ONLY NOTE
 ITEMS APPLICABLE TO THIS PROJECT IF YOU WISH TO USE
 HIGHLIGHTING OR CIRCLING AS A METHOD TO ASSIST WITH
 PLAN REVIEW AND INSPECTIONS.
  
 3. HORIZONTAL INSTALLATIONS TYPICALLY SHOULD USE THE
 HOLLOW BLOCK CHART (SEE SHEET 4) AS THEY ARE FILLED
 CELLS RATHER THAN FORMED AND POURED CONCRETE. EITHER
 PROVIDE EVIDENCE THAT THE SUBSTRATE IS FORMED AND
 POURED AT SIDES OF EACH OPENING, OR USE THE ANCHOR
 SPACING FOR HOLLOW BLOCK, FBC 301.1.
  