| 2012-06-22 14:18:16 | 315 SOUTH FLAGLER DRIVE | | | TRACKING #12060445 | | | MASTER #12010646 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET FP1.2: PROVIDE HIGH-TEMPERATURE AUTOMATIC WET | | | SPRINKLERS AS A BACK-UP SYSTEM TO THE CLEAN AGENT | | | (FM200) SUPPRESSION SYSTEM IN SERVER ROOM #114. | | | | | | WESLEY JOLIN | | | WPB FIRE RESCUE | | | OFFICE OF THE FIRE MARSHAL |
|