| Plan Review Notes For Permit 12060437 |
| Permit Number |
12060437 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-15 13:35:50 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | 2010 FBC. | | | | | | 1- FLAT ROOF NOA 07-1219.09: CLEARLY SPECIFY WHICH FLAT | | | ROOF APPROVED ASSEMBLY AND BASE SHEET FASTENING OPTION | | | IS GOING TO BE USED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NEED RAS 117 CALCULATIONS TO MEET THE DESIGN | | | PRESSURES OF SEC. R301.2.1.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|