Plan Review Notes
Plan Review Notes For Permit 12060428
Permit Number 12060428
Review Stop B
Sequence Number 3
Notes
Date Text
2012-09-12 08:57:35RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- ENGINEER (H. JOHN GRIFFIN II) SPECIFIES MAXIMUM
 DESIGN PRESSURES NOT TO EXCEED -56.0PSF FOR CORNERS AND
 PERIMETERS. THIS IS INCORRECT. ENGINEER TO PROVIDE THE
 DESIGN PRESSURES CALCULATIONS FOR EXPOSURE "C" AS
 REQUIRED BY SEC. R301.2.1.4.3 OF 2010 FLORIDA
 RESIDENTIAL CODE. DESIGN PRESSURES FOR PERIMETER AND
 CORNER AREAS ARE HIGHER THAN -56.0PSF.
 SEC. 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 2- ENGINEER TO REVIEW NOA SUBMITTED AND SPECIFIC
 APPROVED ASSEMBLY TO BE INSTALLED. THEN, PROVIDE THE
 ACTUAL RAS 117 CALCULATIONS. INFORMATION SUBMITTED IS
 NOT PROVIDING THE RAS 117 CALCULATIONS. ENGINEER NEEDS
 TO REVIEW RAS 117 STANDARD. THERE IS A DIFFERENCE ON
 THE FASTENER NUMBER AND SPECIFIC FASTENER ATTACHMENT
 PATTERN FOR ROOF ASSEMBLIES WITH INSULATION AND ROOF
 ASSEMBLIES WITHOUT INSULATION. PROVIDE COMPLETE
 CALCULATIONS AND FASTENER PATTERN AS REQUIRED BY RAS
 117. SEC. 107.2.1.2 OF CITY AMENDMENTS TO FBC.
  
 IF ENGINEER HAS ANY QUESTIONS AFTER REVIEWING RAS 117
 STANDARD, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  