2012-06-15 11:44:18RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 2010 FLORIDA BUILDING CODES.
  
 1- CLEARLY SPECIFY WHICH APPROVED ASSEMBLY FROM NOA
 08-1112.14 SUBMITTED IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE.
 NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE
 USED IN THIS BUILDING. THEY DON'T MEET THE REQUIRED
 DESIGN PRESSURES.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED TO MEET THE DESIGN PRESSURES REQUIRED
 BY SEC. R301.2.1.4.3.
  
 NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON
 EXPOSURE "C".
  