| Plan Review Notes For Permit 12060428 |
| Permit Number |
12060428 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-15 11:44:18 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | 2010 FLORIDA BUILDING CODES. | | | | | | 1- CLEARLY SPECIFY WHICH APPROVED ASSEMBLY FROM NOA | | | 08-1112.14 SUBMITTED IS GOING TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE. | | | NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE | | | USED IN THIS BUILDING. THEY DON'T MEET THE REQUIRED | | | DESIGN PRESSURES. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NEED TO MEET THE DESIGN PRESSURES REQUIRED | | | BY SEC. R301.2.1.4.3. | | | | | | NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | | TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON | | | EXPOSURE "C". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|