2012-06-18 15:09:53RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 07-1219.09 SUBMITTED. NEED RAS 117 CALCULATIONS TO MEET
 THE DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF
 2010 FLORIDA RESIDENTIAL CODE.
  
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS
 BUILDING IS LOCATED ON EXPOSURE "C". SEC. R301.2.1.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712